Coil End Lead Cable BS6195

  • Description
  • Specification
  • Part Options

Coil End Leads, conforming to BS6195 standards, feature flexible tinned copper conductors with Ethylene Propylene Rubber (EPR) insulation, offering heat, oil, and flame resistance (HOFR). Ideal for electrical machinery and panel wiring, they provide a flexible, direct connection to coil windings in various equipment like motors, transformers, and circuit breakers. Their HOFR sheath prevents lubricant penetration, making them suitable for environments requiring oil resistance. Additionally, these cables find applications in the railway industry as an anode cable. 

  • Conductor

    Tinned Copper

  • Stranding

    Class 5

  • Insulation

    EPR

  • Outersheath

    CSP

  • Outersheath Colour

    Black

  • Minimum Bending Radius

    Fixed: 4 x overall diameter / Flexed: 6 x overall diameter

  • Operating Temperature

    Maximum 90°C, Minimum bending -30°C

  • Standards

    BS6195 Type 4 (Where applicable) flexible cables, insulated, for coil leads

BATT Part No  Cable Type Voltage rating (kv) No of cores Nominal cross sectional area of conductor (mm2) Nominal thickness of insulation (mm) Approx overall diameter (mm) Weight (kg/km)
23009 4A 300/500 1 0.75 0.8 3.5 16
23015 4A 300/500 1 1 0.8 3.7 19
23021 4A 300/500 1 1.5 0.8 4 29
23028 4A 300/500 1 2.5 0.9 4.6 42
23034 4A 300/500 1 4 1 5.4 61
23037 4A 300/500 1 6 1 6.5 88
23041 4A 300/500 1 10 1.2 7.9 141
23022 4C 0.6/1 1 1.5 1.4 4.3 34
23003 4C 0.6/1 1 2.5 1.4 4.8 45
23035 4C 0.6/1 1 4 1.4 5.4 70
23038 4C 0.6/1 1 6 1.5 6.2 97
23043 4C 0.6/1 1 10 1.5 8.5 130
23045 4C 0.6/1 1 16 1.5 9.6 190
23049 4C 0.6/1 1 25 1.6 11.4 290
23052 4C 0.6/1 1 35 1.6 12.8 380
23057 4C 0.6/1 1 50 1.7 14.8 510
23064 4C 0.6/1 1 70 1.8 17.2 750
23070 4C 0.6/1 1 95 2 19.7 935
23073 4C 0.6/1 1 120 2.2 21.9 1160
23080 4C 0.6/1 1 150 2.3 24.1 1450
23083 4C 0.6/1 1 185 2.4 26.3 1770
23084 4C 0.6/1 1 240 2.4 28.3 2260
23001 4C 0.6/1 1 300 2.6 33 2760
23030 4C 0.6/1 1 400 2.8 37.4 3880
23032 4D 1.9/3.3 1 2.5 2.8 8.5 100
23046 4D 1.9/3.3 1 16 2.8 12.4 288
23050 4D 1.9/3.3 1 25 2.8 13.8 392
23053 4D 1.9/3.3 1 35 2.8 15.2 509
23058 4D 1.9/3.3 1 50 2.8 17.1 682
23065 4D 1.9/3.3 1 70 2.8 19.2 894
23074 4D 1.9/3.3 1 120 5 27.8 1634
23039 4D 1.9/3.3 1 240 3 30.6 2657
23029 4D 1.9/3.3 1 400 3 37.8 4229
23044 4E 3.8/6.6 1 16 5 17.2 408
23059 4E 3.8/6.6 1 50 5 22.1 832
23047 4F 6.35/11 1 16 7.6 22.9 255
23060 4F 6.35/11 1 50 7.6 27.3 1114
23068 4F 6.35/11 1 70 7.6 29.4 1344
23012 4F 6.35/11 1 95 7.6 31.5 1610

ELECTRICAL CHARACTERISTICS

Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables

Nominal cross sectional area (mm2) Maximum diameter of wires in conductor (mm) Maximum resistance of conductor at 20ºC (ohms/km) - Metal Coated Wires
0.75    
1.5 0.26 13.7
2.5 0.26 8.21
4 0.31 5.09
6 0.31 3.39
10 0.41 1.95
16 0.41 1.24
25 0.41 0.795
35 0.41 0.565
50 0.41 0.393
70 0.51 0.277
95 0.51 0.210
120 0.51 0.164
150 0.51 0.132
185 0.51 0.108
240 0.51 0.0817
300 0.51 0.0654
400 0.51 0.0495

 

Batt Part No. Voltage rating (kv) Core Size Colour/Reference
23009 300/500 1 0.75 Black
23015 300/500 1 1 Black
23021 300/500 1 1.5 Black
23022 0.6/1 1 1.5 Black
23028 300/500 1 2.5 Black
23003 0.6/1 1 2.5 Black
23032 3.3 1 2.5 Black
23034 300/500 1 4 Black
23035 0.6/1 1 4 Black
23037 300/500 1 6 Black
23038 0.6/1 1 6 Black
23041 300/500 1 10 Black
23043 0.6/1 1 10 Black
23045 0.6/1 1 16 Black
23046 1.9/3.3 1 16 Black
23044 3.8/6.6 1 16 Black
23047 6.35/11 1 16 Black
23049 0.6/1 1 25 Black
23050 1.9/3.3 1 25 Black
23052 0.6/1 1 35 Black
23053 1.9/3.3 1 35 Black
23057 0.6/1 1 50 Black
23058 1.9/3.3 1 50 Black
23059 3.8/6.6 1 50 Black
23060 6.35/11 1 50 Black
23064 0.6/1 1 70 Black
23065 1.9/3.3 1 70 Black
23068 6.35/11 1 70 Black
23070 0.6/1 1 95 Black
23012 6.35/11 1 95 Black
23073 0.6/1 1 120 Black
23074 1.9/3.3 1 120 Black
23080 0.6/1 1 150 Black
23083 0.6/1 1 185 Black
23084 0.6/1 1 240 Black
23039 1.9/3.3 1 240 Black
23001 0.6/1 1 300 Black
23030 0.6/1 1 400 Black
23029 1.9/3.3 1 400 Black

The information in this datasheet is for guidance only and subject to change without liability. Images provided are representations; actual cable dimensions may vary due to manufacturing tolerances.