Conductor: Bare copper, class 1 or class 2 to IEC 60228
Insulation: Cross-linked Polyethylene (XLPE)
Core identification: According to HD 308
2 core brown - blue
3 core brown - blue - green/yellow
4 core brown - grey - black - green/yellow
5 core brown - grey - black - blue - green/yellow
Filler: Extruded plastic bland
Jacket: Low Smoke Zero Halogen (LSZH)
Jacket Colour: Green
Voltage rating: 600/1000V
Test Voltage: 4000 V
Temperature: -20°C + 90 °C
Min. bending radius : 6 x D
Standards: NBN HD 604 5L
Flame retardant to : EN 60332-3-1-2
Fire retardant to : EN 60332-3-24, NBN C30-004 F2
Halogen Free to : EN 50267-2-1, EN 50267-2-2
Low Smoke Emission : EN 61034-2
Whilst BATT CABLES plc endeavours to ensure the information on the website, specification sheets and all other technical information is accurate, the information is for guidance only and it is subject to change without notice or liability. Batt Cables Plc is not responsible for the consequences of any inadequacies, inaccuracies or other deficiencies contained therein. When selecting cable accessories, please note that the actual cable dimensions may vary due to manufacturing tolerances.
Batt Part No. | Core | Size | Colour/Reference | Quote |
---|---|---|---|---|
30029 | 2 | 1.5 | Get Quote | |
30021 | 3G | 1.5 | Get Quote | |
30020 | 3G | 2.5 | Get Quote | |
33016 | 3G | 4 | Get Quote | |
30022 | 5G | 2.5 | Get Quote | |
30023 | 5G | 2.5 | Get Quote | |
30010 | 5G | 4 | Get Quote | |
30011 | 5G | 6 | Get Quote | |
30012 | 5G | 10 | Get Quote | |
30013 | 5G | 16 | Get Quote |