Applications: Protected and fixed installation inside electrical equipment, especially suitable for the connection of motor windings, switchboards, white goods and lighting fixtures.
Conductor: Stranded tin plated copper, according to IEC 60228, class 5
Insulation: Radox® 125. Extruded and electron beam cross linked polyolefin copolymer
Core colours: Various, on request
Technical data
Voltage rating Uo/U ≤0.50mm²: 450 / 750 V AC
Test voltage ≤0.50mm²: 2500 V AC
Voltage rating Uo/U ≥0.50mm²: 600 / 1000 V AC
Test voltage≥0.50mm²: 3500 V AC
Temperature range: -40°C up to + 125°C
Features: Excellent high and low temperature and ozone resistant, Weather-proof, halogen free, flexible – easy to strip and process, flame retardant, high resistance to thermal pressure, high abrasion resistance, oil resistant
Standards: Fire Tests
Content of halogen acid gas: IEC 60754-1, EN 50267-2-1 0mg/g
Corrosivity of combustion gasses: IEC 60754-2, EN 50267-2-3
Smoke density: IEC 61034-2, EN50268-2