RE2Y(st)YSWAY fl Instrumentation Cable

Application: For transmission of analogue and digital signals in instrument and control systems, allowed for use in zone 1 and zone 2 group ii classified areas (IEC 60079-14). Not allowed for direct connection to low impedance source e.g. the public mains electricity supply.

Conductor: Plain annealed copper sizes 0.5mm², 0.75mm², 1.0mm², 1.3mm², 1.5mm², 2.5mm² IEC 60228 class 1, 2 or 5.

Insulation: PE

Colour code: Black / White numbered for multi-pairs

Collective screen: 24µ aluminium / PETP tape over 7 stranded tinned copper drain wire, 0.5mm²

Inner sheath: PVC

Armouring: Galvanised steel wire armour

Outer sheath: PVC

Min bending radius: 10 x cable OD

Standards: EN50288-7:2005 Multi-element metallic cables used in analogue and digital communication and control. Part 7 - sectional specification for instrumentation and control cables. Flame retardant to IEC60332-3, Oil resistant to ICEA S-82-552, UV resistant to UL 1581. This cable type is suitable for use in Zone 1 and Zone 2 only when installed with the correct ATEX Approved Accessories/Equipment

Whilst BATT CABLES plc endeavours to ensure the information on the website, specification sheets and all other technical information is accurate, the information is for guidance only and it is subject to change without notice or liability. Batt Cables Plc is not responsible for the consequences of any inadequacies, inaccuracies or other deficiencies contained therein. When selecting cable accessories, please note that the actual cable dimensions may vary due to manufacturing tolerances.  

Technical Information

Batt Part No. Core Size Colour/Reference Quote
86504 12 1.5mm2 Get Quote