BATT Part Number:91390
Type:9841/SWA/PVC
Nominal voltage rating:300 / 300 volts
Conductors
Material:Tinned copper class 2
No of pairs:1
No of cores:2
Nominal cross section:24 AWG (circa 0.22sqmm)
Insulation of conductors
Material:PE
Insulation thickness:0.27mm
Insulation diameter:1.15 +/- 0.1
Colour:White and Blue / Blue and White
Overall shielding
Material:All / Polyester tape
Drain wire:Tinned copper / AWG 24
Tinned copper wire braid:Tinned copper
Bedding
Material:PVC
Nominal diameter:4.00 mm
Armouring: SWA
Material:Steel wires
Diameter over armour:5.80mm
Outer Sheath
Material:PVC
Nominal thickness:1.30mm
Nominal outer diameter:8.4 +/- 0.50 mm
Max DC Resistance per core at 20°C: < 80 Ohm/Km
Max insulation resistance at 20°C: >5 G Ohm/Km
Standard: IEC 60332
Whilst BATT CABLES plc endeavours to ensure the information on the website, specification sheets and all other technical information is accurate, the information is for guidance only and it is subject to change without notice or liability. Batt Cables Plc is not responsible for the consequences of any inadequacies, inaccuracies or other deficiencies contained therein. When selecting cable accessories, please note that the actual cable dimensions may vary due to manufacturing tolerances.
Batt Part No. | Core | Size | Colour/Reference | Quote |
---|---|---|---|---|
91390 | 2 | 24mm2 | Get Quote |