| Applications: |
Can be used for control voltages and data transfer in alarm and fire alarm systems, where a circuit integrity acc. to DIN 4102-12 is required. For fixed installation in dry and wet rooms. |
| |
|
| Type of Cable |
Cu / SILICON RUBBER / CAM / LSOH |
| |
|
| |
|
| Standard |
DIN VDE 0815 |
| |
|
| Nominal voltage rating |
300 / 500 V |
| |
|
| Conductors: |
|
| Material |
Plain Annealed Copper Class 1 |
| No. Of Pairs |
1 |
| No. Of Cores |
2 |
| Nominal cross section |
0.5mm² |
| Conductor diameter |
0.8mm |
| |
|
| Insulation of conductors: |
|
| Material |
SILICON RUBBER |
| Minimum average thickness |
0.55mm |
| minimum thickness at any point |
0.5mm |
| Approx outer diameter (over insulation) |
1.9mm |
| Colour: |
red - blue |
| |
|
| Overall shielding |
|
| Material |
Polyester - Fiber Glass Tape - All/Polyester tape |
| Drain wire |
tinned copper 0,8 mm |
| |
|
| Bedding: |
|
| Material |
LSOH |
| Nominal thickness |
1mm |
| Approx. Diameter over bedding |
6,3 +/- 1,5 mm |
| Printing |
|
| |
|
| Maximum DC Resistance per core at 20°C |
< 36,0 Ohm/Km |
| |
|
| Max. insulation resistance at 20°C |
> 1 Gohm/km |
| |
|
| Minimum allowable bending radius |
6 x overall diameter |