Accessibility Page Navigation
Style sheets must be enabled to view this page as it was intended.
Print Header
Border Top

Fire Resistant Enhanced Cable

These cables meet the enhanced requirements of BS5839-1 providing advanced resistance to fire & heat and is therefore suitable as fire alarm cable 

Conductors: Plain annealed solid copper to BS EN60228 and IEC60228 (up to 2.5sqmm) or stranded copper (4.0sqmm and above)

Enhanced Insulation: Special cross-linked heat resistance compound type E12 acc. to BS EN 50363.1


Core identification: 2 Core: Blue & brown, 3 core: Blue, brown & grey, 4 core: Black, Blue, brown & grey

Enhanced Electrostatic Screen: Aluminium/polyester laminated tape 

Enhanced Sheath/Jacket: Thermoplastic zero halogen, low smoke (OHLS) compound

Colour: Red or white

Voltage: 300/500v

Operating temperature: Maximum 70°C, minimum -30°C

Standards:
BS5839-1:2002 enhanced performance

Flame Propagation BS EN 60332-1-2,  BS EN 50266-2-2 
Smoke Emission  BS EN 61034-2
Gases evolved during combustion BS EN 50267-2-1 HCL≤0.5%

Approvals: BASEC, LPCB

Applications: These cables meet the enhanced requirements of BS5839-1 2002 and additionally meets the requirements for integrated water spray and mechanical shock

Technical Information

Batt Part No. Core Size Colour/Reference Quote
44314 2 1.5sqmm White Get Quote
44313 2 1.5sqmm Red Get Quote
44373 2 2.5sqmm White Get Quote
44337 2 2.5sqmm Red Get Quote
44338 3 1.5sqmm Red Get Quote
44374 4 1.5sqmm Red Get Quote