These cables meet the enhanced requirements of BS5839-1 providing advanced resistance to fire & heat and is therefore suitable as fire alarm cable
Conductors: Plain annealed solid copper to BS EN60228 and IEC60228 (up to 2.5sqmm) or stranded copper (4.0sqmm and above)
Enhanced Insulation: Special cross-linked heat resistance compound type E12 acc. to BS EN 50363.1
Core identification: 2 Core: Blue & brown, 3 core: Blue, brown & grey, 4 core: Black, Blue, brown & grey
Enhanced Electrostatic Screen: Aluminium/polyester laminated tape
Enhanced Sheath/Jacket: Thermoplastic zero halogen, low smoke (OHLS) compound
Colour: Red or white
Voltage: 300/500v
Operating temperature: Maximum 70°C, minimum -30°C
Standards:
BS5839-1:2002 enhanced performance
Flame Propagation BS EN 60332-1-2, BS EN 50266-2-2
Smoke Emission BS EN 61034-2
Gases evolved during combustion BS EN 50267-2-1 HCL≤0.5%
Approvals: BASEC, LPCB
Applications: These cables meet the enhanced requirements of BS5839-1 2002 and additionally meets the requirements for integrated water spray and mechanical shock



| Batt Part No. | Core | Size | Colour/Reference | Quote |
|---|---|---|---|---|
| 44314 | 2 | 1.5sqmm | White | Get Quote |
| 44313 | 2 | 1.5sqmm | Red | Get Quote |
| 44373 | 2 | 2.5sqmm | White | Get Quote |
| 44337 | 2 | 2.5sqmm | Red | Get Quote |
| 44338 | 3 | 1.5sqmm | Red | Get Quote |
| 44374 | 4 | 1.5sqmm | Red | Get Quote |