15kv SWA mains armoured power cable to BS7835 and IEC60502-2
Conductor: Plain annealed stranded compacted copper
Core identification: Coloured tape under the screen
Insulation: XLPE (Cross linked polyethylene)
Screen: Semi-conducting layer with a copper tape screen covering each core
Bedding: LSZH (Low Smoke Zero Halogen)
Armour/Protection: SWA (Single wire armour)
Sheath/Jacket: LSZH (Low Smoke Zero Halogen)
Operating temperature: Maximum 90°C, minimum bending 0°C.
Standards: BS7835 (LSZH) : Specification for armoured cables with extruded cross-linked polyethylene or ethylene propylene rubber insulation for rated voltages from 3.8/6.6kV up to 19/33kV having low emission of smoke and corrosive gases when affected by fire
IEC60502-2: Power cables with extruded insulation and their accessories for rated voltages from 6kV to 30kV (Um=36kV)



| Batt Part No. | Core | Size | Colour/Reference | Quote |
|---|---|---|---|---|
| 56546 | 3 | 70sqmm | Red | Get Quote |
| 56547 | 3 | 120sqmm | Red | Get Quote |
| 56634 | 3 | 185sqmm | Red | Get Quote |
| 56548 | 3 | 240sqmm | Red | Get Quote |