RE-2X(St)YSWAY CAM/SWA/PVC Instrumentation Cable

RE-2X(St)YSWAY CAM/SWA/PVC Instrumentation Cable

Applications: RE2XSTY SWAY instrumentation cable to EN50288-7, suitable for instrumentation, control and communications applications. Suitable for direct burial.

Conductors: Class 2 copper conductors plus comms core, 0.75sqmm pair, 1.3sqmm pairs & triples and 1.5sqmm pairs & triples

Insulation: XLPE to EN50290-2-29

Pair identification: Black & white numbered

Triple identification: Black, white and red numbered

Screen: CAM (Collective aluminium mylar) including drain wire

Bedding: PVC

Sheath/Jacket: PVC (Polyvinyl-Chloride) RP

Armour: SWA (Steel wire armour)

Colour: Black or Blue

Voltage: 500v

Insulation thickness: 0.44mm

Tinned copper drain wire: 0.5sqmm

Sheath thickness:
1 Pair 1.3m, 2-4 pairs 1.4mm, 8 pairs 1.5mm
1 Triple 1.3sqmm 1.3mm, 1.5sqmm 1.4mm

Armour wire diameter:
1-4 pairs: 0.9mm, 8 pairs 1.5mm, 1 triple 0.9mm

Bedding thickness: 1.00mm

Installation temperature range: -5 to +90 deg C

Operation temperature range -30 to +90 deg C

Core temperature: +90 deg C

Designation:
RE Instrumentation
2X XLPE insulation
2Y PE insulation
Y PVC insulation
ST CAM
Y PVC sheath
SWA Steel wire armour
Y PVC sheath

Standards: EN50288-7:2005 Multi-element metallic cables used in analogue and digital communication and control. Part 7 - sectional specification for instrumentation and control cables. Flame retardant to IEC60332-3, Oil resistant to ICEA S-82-552, UV resistant to UL 1581. This cable type is suitable for use in Zone 1 and Zone 2 only when installed with the correct ATEX Approved Accessories/Equipment

Whilst BATT CABLES plc endeavours to ensure the information on the website, specification sheets and all other technical information is accurate, the information is for guidance only and it is subject to change without notice or liability. Batt Cables Plc is not responsible for the consequences of any inadequacies, inaccuracies or other deficiencies contained therein. When selecting cable accessories, please note that the actual cable dimensions may vary due to manufacturing tolerances.  

 

Technical Information

Batt Part No. Core Size Colour/Reference Quote
85987 1 pair 0.75sqmm Black Get Quote
85988 1 pair 0.75sqmm Blue Get Quote
85989 1 pair 1.3sqmm Black Get Quote
85990 1 pair 1.3sqmm Blue Get Quote
85991 1 pair 1.5sqmm Black Get Quote
86200 1 pair 1.5sqmm Blue Get Quote
85995 1 triple 1.3sqmm Black Get Quote
85996 1 triple 1.3sqmm Blue Get Quote
85997 1 triple 1.5sqmm Black Get Quote
86201 1 triple 1.5sqmm Blue Get Quote
85992 2 pair 0.75sqmm Black Get Quote
85993 4 pair 0.75sqmm Black Get Quote
85994 8 pair 0.75sqmm Black Get Quote
86652 2 pair 0.75sqmm Blue Get Quote
86656 4 pair 0.75sqmm Blue Get Quote
86660 8 pair 0.75sqmm Blue Get Quote
86970 2 pair 1.5sqmm Black Get Quote
86971 2 pair 1.5sqmm Blue Get Quote
86972 5pair 1.5sqmm Black Get Quote
86972 5pair 1.5sqmm Blue Get Quote
86974 10pair 1.5sqmm Black Get Quote
86975 10pair 1.5sqmm Blue Get Quote