Accessibility Page Navigation
Style sheets must be enabled to view this page as it was intended.
Print Header
Border Top

15KV Single Core AWA PVC Cable BS6622 IEC60502-2

15KV Single Core AWA PVC Cable BS6622 IEC60502-2

15kv AWA mains armoured power cable to BS6622 and IEC60502-2 

Conductor: Plain annealed stranded compacted copper

Core identification: Coloured tape under the screen

Insulation: XLPE (Cross linked polyethylene)

Screen: Semi-conducting layer with a copper tape screen covering each core

Bedding: PVC (Polyvinyl chloride) 

Armour/Protection: AWA (Aluminium wire Armour)  

Sheath/Jacket: PVC (Polyvinyl chloride) 

Colour: Red

Operating temperature:  Maximum 90°C, minimum bending 0°C

Standards: BS6622 (PVC) BS6622: Power cables, thermosetting polymer insulated high voltage
or BS7835 (LSZH) : Specification for armoured cables with extruded cross-linked polyethylene or ethylene propylene rubber insulation for rated voltages from 3.8/6.6kV up to 19/33kV having low emission of smoke and corrosive gases when affected by fire

IEC60502-2: Power cables with extruded insulation and their accessories for rated voltages from 6kV to 30kV (Um=36kV)  


Applications: mains power transmission cables

Whilst BATT CABLES plc endeavours to ensure the information on the website, specification sheets and all other technical information is accurate, the information is for guidance only and it is subject to change without notice or liability. Batt Cables Plc is not responsible for the consequences of any inadequacies, inaccuracies or other deficiencies contained therein. When selecting cable accessories, please note that the actual cable dimensions may vary due to manufacturing tolerances.  

Technical Information

Batt Part No. Core Size Colour/Reference Quote
56259 1 300sqmm Black Get Quote
Border Bottom