BS6724 AWA LSZH Cable IEC 60502 600/1000V

BS6724 AWA LSZH Cable IEC 60502 600/1000V
Applications: Power cable suitable for power networks and direct burial, where fire and emissions of smoke and toxic fumes create a serious potential threat. Armoured LSZH power cable to British Standard BS6724 & IEC 60502 suitable for mains power networks

Conductors: Plain annealed stranded copper

Conductor stranding: Class 2 - stranded circular or circular compacted

Insulation: XLPE (Cross linked polyethylene)

Core identification: Brown

Bedding: LSZH (Low smoke zero halogen)

Armour/Protection: AWA (Aluminium wire armour) non-magnetic

Sheath/Jacket: LSZH (Low smoke zero halogen)

Colour: Black

Voltage: 600/1000v

Operating temperature Maximum 90°C

Conductor identification: Brown

Minimum bending radius: 6 x Overall diameter (wherever possible, larger installation radi should be used)

Combustion characteristics: Oxygen index: 35 (Temperature index 280°C)
HCL emission 0.5% in accordance with BSEN50267-1 common test methods for cables under fire conditions. Tests on gases evolved during combustion of materials from cables. Procedures, determination of the amount of halogen acid gas.

Standard: BS6724: Electric cables. Thermosetting insulated, armoured cables for voltages of 600/1000V and 1900/3300V, having low emission of smoke and corrosive gases when affected by fire BSEN50267-1 Common test methods for cables under fire conditions. Tests on gases evolved during combustion of materials from cables. Apparatus BSEN50267-2-1:Common test methods for cables under fire conditions. Tests on gases evolved during combustion of materials from cables. Procedures. Determination of the amount of halogen acid gas BSEN50266-1 Common test methods for cables under fire conditions. Test for vertical flame spread of vertically-mounted bunched wires or cables
IEC 60502: Power cables with extruded insulation and their accessories for rated voltages from 1kV to 30kV
BSEN/IEC60332-1-2: Tests on electric and optical fibre cables under fire conditions Part 1: test for vertical flame propagation for a single insulated wire or cable Section 2: procedure for 1kW pre-mixed flame
BSEN61034-2:2005 Measurement of smoke density of cables burned under defined conditions. Test procedure and requirements
Flame Propagation Test to BS EN 60332-1-2:2004 for single cable and BS EN 60332-3-24:2009 (Cat C) for multiple cables

Notes: For current rating refer to Table 4E3A. If you are considering installing in high UV exposure and/or high/low ambient temperatures i.e. desert/arctic conditions then special sheathing may be required

 

Whilst BATT CABLES plc endeavours to ensure the information on the website, specification sheets and all other technical information is accurate, the information is for guidance only and it is subject to change without notice or liability. Batt Cables Plc is not responsible for the consequences of any inadequacies, inaccuracies or other deficiencies contained therein. When selecting cable accessories, please note that the actual cable dimensions may vary due to manufacturing tolerances.  

Technical Information

Batt Part No. Core Size Colour/Reference Quote
56415 1 50sqmm Black Get Quote
56416 1 70sqmm (Class 2) Black Get Quote
56417 1 95sqmm (Class 2) Black Get Quote
56418 1 120sqmm (Class 2) Black Get Quote
56419 1 150sqmm (Class 2) Black Get Quote
56420 1 185sqmm (Class 2) Black Get Quote
56421 1 240sqmm (Class 2) Black Get Quote
56422 1 300sqmm (Class 2) Black Get Quote
56423 1 400sqmm (Class 2) Black Get Quote
56424 1 500sqmm (Class 2) Black Get Quote
56425 1 630sqmm (Class 2) Black Get Quote
56426 1 800sqmm (Class 2) Black Get Quote
56427 1 1000sqmm (Class 2) Black Get Quote