Accessibility Page Navigation
Style sheets must be enabled to view this page as it was intended.
Print Header
Border Top

Fire Resistant Power Cable BS6387

Fire Resistant Power Cable BS6387

Fire performance power cable to BS6837 suitable as fire alarm cable and emergency lighting cable

Conductor: Plain annealed stranded copper to BSEN60228 (class 2) 

Fire barrier: MGT (Mica glass tape)

Insulation: XLPE (Cross linked polyethylene)

Core identification: 2 core:Brown & blue, 3 core: Brown, black & grey, 4 core: Brown, grey, blue & black, Multicore: White cores with black numerals

Bedding: LSZH (Low smoke zero halogen)

Armour/Protection: SWA (Single wire armour)

Sheath/Jacket: LSZH (Low smoke zero halogen)

Colour: Black

Voltage: 600/1000v

Operating temperature: Maximum 90°C, minimum bending: -0°C, minimum operating: -10°C

Standards: BS6387, Categories C, W & Z, Specification for performance requirements for cables required to maintain circuit integrity under fire conditions
IEC60331: Tests for electric cables under fire conditions - circuit integrity 
BS EN 61034:2005: Measurement of smoke density of cables burned under defined conditions. Test procedure and requirements
BS6724: Electric cables. Thermosetting insulated, armoured cables for voltages of 600/1000V and 1900/3300V, having low emission of smoke and corrosive gases when affected by fire
BS7846: Electric cables. 600/1000 V armoured fire-resistant cables having thermosetting insulation and low emission of smoke and corrosive gases when affected by fire
BS EN 50266:2001: Common test methods for cables under fire conditions. Test for vertical flame spread of vertically-mounted bunched wires or cables

Fire Resistance BS6387 Categories C, W & Z:
IEC60331: 750 deg C for 3 hours
Flame Propagation BS EN 50266 parts 1 and 3, IEC 60332-3, BS EN 60332:2004
Smoke Emission IEC 61034, BS EN 61034:2005
Corrosive Acid Gas BS EN 50267-2-1:1999, IEC 60754-1

Fire resistant to IEC 60331 1-2 

Applications: Fire performance cables maintain circuit integrity in a fire and so are suitable for fire detection, alarm and emergency lighting systems

Minimum Bending Radius:  6 x Overall Diameter for Circular Conductors. 8 x Overall Diameter for Shaped Conductors

 

Whilst BATT CABLES plc endeavours to ensure the information on the website, specification sheets and all other technical information is accurate, the information is for guidance only and it is subject to change without notice or liability. Batt Cables Plc is not responsible for the consequences of any inadequacies, inaccuracies or other deficiencies contained therein. When selecting cable accessories, please note that the actual cable dimensions may vary due to manufacturing tolerances.  

Technical Information

Batt Part No. Core Size Colour/Reference Quote
57183 2 1.5sqmm (Class 2) Black Get Quote
57184 2 2.5sqmm (Class 2) Black Get Quote
57185 2 4.0sqmm (Class 2) Black Get Quote
57186 2 6.0sqmm (Class 2) Black Get Quote
57187 2 10sqmm (Class 2) Black Get Quote
57188 2 16sqmm (Class 2) Black Get Quote
57189 2 25sqmm (Class 2) Black Get Quote
57190 2 35sqmm (Class 2) Black Get Quote
57191 2 50sqmm (Class 2) Black Get Quote
57192 2 70sqmm (Class 2) Black Get Quote
57193 2 95sqmm (Class 2) Black Get Quote
57194 2 120sqmm (Class 2) Black Get Quote
57195 2 150sqmm (Class 2) Black Get Quote
57196 2 185sqmm (Class 2) Black Get Quote
57197 2 240sqmm (Class 2) Black Get Quote
57198 2 300sqmm (Class 2) Black Get Quote
57199 2 400sqmm (Class 2) Black Get Quote
57212 3 1.5sqmm (Class 2) Black Get Quote
57213 3 2.5sqmm (Class 2) Black Get Quote
57214 3 4.0sqmm (Class 2) Black Get Quote
57215 3 6.0sqmm (Class 2) Black Get Quote
57216 3 10sqmm (Class 2) Black Get Quote
57217 3 16sqmm (Class 2) Black Get Quote
57218 3 25sqmm (Class 2) Black Get Quote
57219 3 35sqmm (Class 2) Black Get Quote
57220 3 50sqmm (Class 2) Black Get Quote
57221 3 70sqmm (Class 2) Black Get Quote
57222 3 95sqmm (Class 2) Black Get Quote
57223 3 120sqmm (Class 2) Black Get Quote
57224 3 150sqmm (Class 2) Black Get Quote
57225 3 185sqmm (Class 2) Black Get Quote
57226 3 240sqmm (Class 2) Black Get Quote
57227 3 300sqmm (Class 2) Black Get Quote
57228 3 400sqmm (Class 2) Black Get Quote
57200 4 1.5sqmm (Class 2) Black Get Quote
57201 4 2.5sqmm (Class 2) Black Get Quote
57202 4 4.0sqmm (Class 2) Black Get Quote
57203 4 6.0sqmm (Class 2) Black Get Quote
57204 4 10sqmm (Class 2) Black Get Quote
57205 4 16sqmm (Class 2) Black Get Quote
57236 4 25sqmm (Class 2) Black Get Quote
57230 4 35sqmm (Class 2) Black Get Quote
57237 4 50sqmm (Class 2) Black Get Quote
57243 4 70sqmm (Class 2) Black Get Quote
57231 4 95sqmm (Class 2) Black Get Quote
57232 4 120sqmm (Class 2) Black Get Quote
57233 4 150sqmm (Class 2) Black Get Quote
57234 4 185sqmm (Class 2) Black Get Quote
57254 4 240sqmm (Class 2) Black Get Quote
57235 4 300sqmm (Class 2) Black Get Quote
57253 4 400sqmm (Class 2) Black Get Quote
57247 5 1.5sqmm (Class 2) Black Get Quote
57248 5 2.5sqmm (Class 2) Black Get Quote
57130 7 1.5sqmm (Class 2) Black Get Quote
57142 7 2.5sqmm (Class 2) Black Get Quote
57106 12 1.5sqmm (Class 2) Black Get Quote
57143 12 2.5sqmm (Class 2) Black Get Quote
57145 19 1.5sqmm (Class 2) Black Get Quote
57144 19 2.5sqmm (Class 2) Black Get Quote
57239 27 2.5sqmm (Class 2) Black Get Quote
57125 37 1.5sqmm (Class 2) Black Get Quote
57060 37 2.5sqmm (Class 2) Black Get Quote
57113 48 2.5sqmm Black Get Quote
57247 5 1.5 Get Quote
57248 5 2.5 Get Quote
57249 5 4 Get Quote
57250 5 6 Get Quote
57331 5 10 Get Quote
57329 5 16 Get Quote
57330 5 25 Get Quote
Border Bottom